Manual VIPA System 200V
Chapter 4 Interbus
HB97E - IM - Rev. 06/29
4-5
Interbus is based upon a ring structure that operates as a cyclic shift
register. Every Interbus module inserts a shift register into the ring. The
number of I/O points supported by the module determines the length of this
shift register. A ring-based shift register is formed due to the fact that all
the devices are connected in series and that the output of the last shift
register is returned to the bus master. The length and the structure of this
shift register depend on the physical construction of the entire Interbus
system.
Interbus operates by means of a master-slave access method where the
master also provides the link to any high-level control system. The ring-
structure includes all connected devices actively in a closed communication
loop.
In comparison to client-server protocols where data is only exchanged
when a client receives a properly addressed command, Interbus
communications is cyclic in nature and data is exchanged at constant inter-
vals. Every data cycle addresses all devices on the bus.
Pr
o
c
e
s
s
D
at
a
P
ro
c
e
s
s
D
at
a
Proce s s D
at
a
C
R
C
C o ntrol Loop Back
Protocol Overhead
Start of
Scan
End of
Scan
Data Array
in
out
IBS Master
IBS Slave
IBS Slave
IBS Slave
IBS Param
RS232
Process data
transfer
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...