Manual VIPA System 200V
Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-61
After Power ON, the DP slave executes a self test. It controls its internal
functions and the communication via the backplane bus. After the error free
start-up, the bus coupler switches into the state "ready". In this state, the
DP slave gets its parameters from the DP master and, at valid parameters,
switches into the state "DataExchange" DE (DE is permanently on).
At communication errors at the backplane bus, the Profibus slave switches
into STOP and boots again after app. 2 seconds. As soon as the test has
been completed positive, the RD-LED blinks.
Power On
Project data conform
with real build-up?
Para-
meterization
error?
DP slave receives
project data from DP
master
ER-LED on
PW-LED on
Initialization
DP slave sets outputs
to "0" and takes over
the defined Profibus
address
ER-LED off
RD-LED blinks
RD-LED on
DE-LED on
Release in-/outputs
no
Configuration
error?
no
yes
y
y
ER-LED and
RD-LED blinking
simultaneously
ER-LED and
RD-LED blinking
simultaneously
Data exchange
no
Start-up behavior
IM 253DP slave
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...