Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
21:0
No maintenance indica-
tion
Burner
21:1
to
21:100
The number of hours run
before the burner should
be serviced is adjustable
from 100 to 10000 hours
(each step represents
100 hours)
23:0
No time interval for bur-
ner maintenance
23:1
to
23:24
Time interval adjustable
from 1 to 24 months
24:0
No "Maintenance" dis-
play
24:1
"Maintenance" display
(the address is automati-
cally set and must be
manually reset after
maintenance has been
completed)
25:0
*
1
No recognition of out-
side temperature sen-
sor or remote
monitoring
25:1
Recognition of outside
temperature sensor and
fault monitoring
28:0
No burner interval igni-
tion
28:1
The burner is forced ON
once every 24 hours
2E:0
Without external exten-
sion
2E:1
Including external exten-
sion (automatical adjust-
ment on connection)
2F:0
Venting program dis-
abled
2F:1
Venting program enabled
2F:2
Filling program enabled
30:1
Internal variable speed
circulation pump (auto-
matic adjustment)
30:0
Internal circulation pump
without variable speed
(e.g. temporarily for ser-
vice)
31:65
Set speed of the inter-
nal circulation pump
when operated as boiler
circuit pump 65 %,
defaulted by the boiler
coding card
31:0
to
31:100
Set speed adjustable
from 0 to 100 %
Code 2
(cont.)
44
Coding
56
92
550
GB
*1
Only for constant temperature control units.
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...