Displayed
fault code
Const.
Weat-
her-
comp.
System
character-
istics
Cause
Remedy
F1
X
X
Burner in
fault state
Flue gas tempera-
ture limiter has
responded
Check the
heating sys-
tem water
level. Vent
the heating
system.
Press reset
E
no sooner
than after
20 minutes.
F2
X
X
Burner in
fault state
Temperature limiter
has responded
Check the
heating sys-
tem water
level. Check
the circula-
tion pump.
Vent the heat-
ing system.
Check the
temperature
limiter and
leads.
Press
E
.
F3
X
X
Burner in
fault state
The flame signal is
already present at
burner start
Check the
ionisation
electrode and
leads.
Press
E
.
Checking and acknowledging faults
(cont.)
82
Troubleshooting