Required coding
Address
1 heating circuit with mixer
&
with DHW cylinder
00:4
&
without DHW cylinder
00:3
Function relay of the internal extension: Cylinder loading
pump
53:3
System design 3
With/without DHW heating with low loss header, 1 heating circuit without
mixer and 1 heating circuit with mixer
!
Outside temperature sensor
?
Flow temperature sensor
%
Cylinder temperature sensor
sÖ
Heating circuit pump or boiler
circuit pump
sA
Cylinder loading pump (connec-
tion via external extension H1)
lH
Power supply
aVG
KM BUS
A
External extension H1
B
Low loss header
C
Extension kit for 1 heating circuit
with mixer
D
Maximum temperature controller
(underfloor heating)
Further details regarding the individual steps
(cont.)
26
Initial start-up, inspection, maintenance
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...