Displayed
fault code
Const.
Weat-
her-
comp.
System
character-
istics
Cause
Remedy
bA
X
Mixer M2
continues
to regulate
Communication
fault - extension kit
for mixer circuit M2
Check the
extension kit
connections
and coding.
Start the
extension kit.
bC
X
Control
mode with-
out remote
control
Communication
fault - Vitotrol
remote control
heating circuit A1
Check con-
nections,
cable, coding
address A0
and the
remote con-
trol DIP
switches
bd
X
Control
mode with-
out remote
control
Communication
fault - Vitotrol
remote control
heating circuit M2
bE
X
Control
mode
Vitotrol remote
control incorrectly
encoded
Check the
DIP switch
settings of
the remote
control
bF
X
Control
mode
Incorrect LON com-
munication module
Replace the
LON commu-
nication mod-
ule
C2
X
X
Control
mode
Communication
fault - solar control
unit
Check con-
nections and
coding
address 54
C5
X
X
Control
mode,
max. pump
speed
Communication
fault - variable
speed internal
pump
Check coding
address 30
settings;
check the
heating cir-
cuit pump
DIP switch
settings
Checking and acknowledging faults
(cont.)
79
Troubleshooting
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...