Setting and test values
Set value
Maintenance/
service
Date:
By:
Static pressure
mbar
max. 57.5 mbar
Supply pressure (flow pressure)
=
for natural gas E
mbar
17.4 to
57.5 mbar
=
for natural gas LL
mbar
17.4 to
57.5 mbar
=
for LPG
mbar
42.5 to
57.5 mbar
Tick gas type
Carbon dioxide content CO
2
&
at lower rated output
% by
vol.
&
at upper rated output
% by
vol.
Oxygen content O
2
&
at lower rated output
% by
vol.
&
at upper rated output
% by
vol.
Carbon monoxide content CO
&
at lower rated output
ppm
&
at upper rated output
ppm
Ionisation current
µA
min. 5 µA
Commissioning/service reports
(cont.)
122
Commissioning/service reports
56
92
550