Required coding
Address
Multi-boiler system with Vitotronic 333
01:2
Note
Codes for multi-boiler system, see
Vitotronic 333 installation and operat-
ing instructions.
Connecting the control unit to the LON system (only for
weather-compensated control units)
The LON communication module (accessory) must be plugged in.
Installation instructions
LON communication module
Note
Data transfer via the LON system can take 2 to 3 minutes.
Setting up LON user numbers
Adjust the user number via coding
address 77 (see below).
In a LON system, the same number
cannot
be allocated twice.
Updating the LON user list
Only possible, if all users are connected, and the control unit is encoded as fault
manager (code 79:1).
1.
Press
L
and
d
simultaneously
for approx. 2 seconds. User check
initiated (see page 32).
2.
Press
e
. The user list is updated
after approx. 2 minutes. User
check completed.
Single boiler system with Vitotronic 050 and Vitocom 300
Further details regarding the individual steps
(cont.)
31
Initial start-up, inspection, maintenance
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...