Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
32:0
Signal "External lock-
out" on circulation
pumps: All pumps are
controlled
32:1
to
32:15
Signal "External lockout"
on circulation pumps:
See the following table
Coding
Internal
circula-
tion pump
Heating cir-
cuit pump
Heating cir-
cuit without
mixer
Heating circuit
pump
Heating circuit
with mixer
Cylinder loading
pump
0
Control
funct.
Control funct.
Control funct.
Control funct.
1
Control
funct.
Control funct.
Control funct.
OFF
2
Control
funct.
Control funct.
OFF
Control funct.
3
Control
funct.
Control funct.
OFF
OFF
4
Control
funct.
OFF
Control funct.
Control funct.
5
Control
funct.
OFF
Control funct.
OFF
6
Control
funct.
OFF
OFF
Control funct.
7
Control
funct.
OFF
OFF
OFF
8
OFF
Control funct.
Control funct.
Control funct.
9
OFF
Control funct.
Control funct.
OFF
10
OFF
Control funct.
OFF
Control funct.
11
OFF
Control funct.
OFF
OFF
12
OFF
OFF
Control funct.
Control funct.
13
OFF
OFF
Control funct.
OFF
14
OFF
OFF
OFF
Control funct.
15
OFF
OFF
OFF
OFF
Code 2
(cont.)
45
Coding
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...