Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
Boiler/burner
34:0
Signal "External
demand" on circulation
pumps: All pumps are
controlled
34:1
to
34:23
Signal "External demand"
on circulation pumps:
See the following table
Coding
Internal
circulation
pump
Heating cir-
cuit pump
Heating cir-
cuit without
mixer
Heating cir-
cuit pump
Heating cir-
cuit with
mixer
Cylinder loading pump
0
Control
funct.
Control
funct.
Control funct.
Control funct.
1
Control
funct.
Control
funct.
Control funct.
OFF
2
Control
funct.
Control
funct.
OFF
Control funct.
3
Control
funct.
Control
funct.
OFF
OFF
4
Control
funct.
OFF
Control funct.
Control funct.
5
Control
funct.
OFF
Control funct.
OFF
6
Control
funct.
OFF
OFF
Control funct.
7
Control
funct.
OFF
OFF
OFF
8
OFF
Control
funct.
Control funct.
Control funct.
9
OFF
Control
funct.
Control funct.
OFF
10
OFF
Control
funct.
OFF
Control funct.
11
OFF
Control
funct.
OFF
OFF
12
OFF
OFF
Control funct.
Control funct.
Code 2
(cont.)
46
Coding
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...