Venting the boiler
1.
Close the shut-off valves on the
heating water side.
2.
Connect the drain hose to the boiler
fill & drain valve
B
.
3.
Open valves
A
and
B
, and vent
at mains pressure, until no sound of
escaping air can be heard.
4.
Close valves
A
and
B
, and open
the primary shut-off valves.
Venting the heating system
1.
Close the gas shut-off valve and
start the control unit.
2.
Activate the venting program via
coding address 2F:1.
Note
To call up code 1 and for setting the
coding address, see page 38.
For function and sequence of the
venting program, see page 103.
3.
Check the system pressure.
Further details regarding the individual steps
(cont.)
8
Initial start-up, inspection, maintenance
56
92
550
GB