Heating mode
The set boiler water temperature will
be maintained in the "central heating
and DHW heating"
G
program,
when a demand is raised by the room
temperature-dependent clock thermo-
stat. If no demand is received, the boi-
ler water temperature will be held at
the defaulted frost protection tem-
perature.
DHW heating
The DHW heating will be activated if
the cylinder temperature falls 2.5 K
below the set cylinder temperature.
The burner and the cylinder loading
pump are switched ON. In the deliv-
ered condition, the set boiler tempera-
ture lies 20 K higher than the set DHW
temperature (adjustable in coding
address 60). If the actual cylinder
temperature rises 2.5 K above the set
cylinder temperature, the burner will
be switched OFF and the cylinder
loading pump run-on time will be acti-
vated.
A
Heating programs
B
Comfort mode
C
Information
D
Basic settings
E
Confirmation/acknowledgement
F
Setting values
G
DHW temperature
H
Emissions test function
K
Boiler water temperature
Constant temperature control units
95
Function description
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...