Setting and test values
Set value
Initial start-up
Date:
By:
Static pressure
mbar
max. 57.5 mbar
Supply pressure (flow pressure)
=
for natural gas E
mbar
17.4 to
57.5 mbar
=
for natural gas LL
mbar
17.4 to
57.5 mbar
=
for LPG
mbar
42.5 to
57.5 mbar
Tick gas type
Carbon dioxide content CO
2
&
at lower rated output
% by
vol.
&
at upper rated output
% by
vol.
Oxygen content O
2
&
at lower rated output
% by
vol.
&
at upper rated output
% by
vol.
Carbon monoxide content CO
&
at lower rated output
ppm
&
at upper rated output
ppm
Ionisation current
µA
min. 5 µA
Commissioning/service reports
118
Commissioning/service reports
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...