Checking the thermocouple
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 90 °C:
&
Pull the leads from
thermocouple
A
.
&
Check the continuity of the thermo-
couple with a multimeter.
&
Remove the faulty thermocouple.
&
Install a new thermocouple.
&
After commissioning, press reset
button
E
on the control unit.
Checking and replacing pressure differential sensor
Check the sensor in case of fault messages concerning the differential pressure
sensor:
&
Correct installation
&
Electrical connection
&
Correct position of the O-rings inside the adaptor
&
Are the test nipples closed with plugs?
Replace the sensor if fault messages persist.
Repairs
(cont.)