4.
E
in the display indicates that the
burner control unit is locked out.
After the fault has been removed,
acknowledge by pressing reset
E
.
Fault display design
A
Fault symbol
B
Plain text fault display (only for
weather-compensated control
units)
C
Fault number
D
Fault code
Plain text fault display
&
Burner control unit
&
Outside temperature sensor
&
Flow sensor
&
Boiler sensor
&
Mixed flow sensor
&
DHW cylinder sensor
&
Flue gas sensor
&
DHW outlet sensor
&
Room temperature sensor
&
Collector sensor
&
Solar DHW sensor
&
Remote control
1. Calling up acknowledged fault
messages
Press
d
for approx. 3 seconds.
The fault will then be displayed.
2.
Select the acknowledged fault
with
a
or
b
.
Checking and acknowledging faults
Weather-compensated control units
Red fault indicator
U
flashes for all
faults.
A fault message code flashes in the
programming unit display when a fault
message is issued.
Any fault codes present may be called
up with
a
or
b
.
Call up current fault codes
(cont.)
75
Troubleshooting
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...