Scanning and resetting the "Maintenance" display
The red fault indicator flashes when the limits set via coding address 21 and 23
have been reached. As regards the operating interface display:
&
For constant temperature control units, the hours run (subject to setting) or
the given time interval and the clock symbol flashes.
&
For weather-compensated control units "Maintenance" flashes.
Note
Set code 24:1 and then code 24:0, if maintenance is implemented before main-
tenance is displayed; the set maintenance parameters for hours run and interval
are then reset to 0.
1.
Press
c
.
Maintenance scan is activated.
2.
Scan maintenance messages
with
a
or
b
.
3.
Press
d
, for weather-compen-
sated control units also confirm the
display "Acknowledge: Yes"
with
d
.
"Maintenance" is cancelled from
the display and the red fault indica-
tor continues to flash.
Note
An acknowledged maintenance
message can be redisplayed by
pressing
d
(approx. 3 seconds).
After maintenance has been carried
out
1.
Reset code 24:1 to 24:0.
The red fault indicator is extin-
guished.
Note
If coding address 24 is not reset, a
new "Maintenance" message will
be displayed on Monday at
07:00 h.
2.
If required:
&
Press
c
.
&
Reset burner hours run, burner
starts and consumption (see
page 70).
&
Press
c
.
Further details regarding the individual steps
(cont.)
37
Initial start-up, inspection, maintenance
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...