Checking the burner gauze assembly
Replace the burner gauze assembly if the wire mesh is damaged.
1.
Remove electrodes
A
.
2.
Turn thermal insulation ring
B
clockwise and remove.
3.
Release the eight Torx screws
C
and remove the burner gauze
assembly
D
.
4.
Remove the old gauze assembly
gasket
E
.
5.
Insert a new burner gauze assem-
bly with a new gasket, and secure
with eight Torx screws.
Note
Torque: 4.5 Nm
6.
Refit the thermal insulation ring
B
.
Checking and adjusting the ignition and ionisation electro-
des
A
Ionisation electrode
B
Ignition electrodes