6.
Set the upper rated output.
Constant temperature control units:
&
With
a
/
b
in the display, select
2.
Weather-compensated control
units:
&
With
a
/
b
in the display, select
"Full load".
7.
Check the CO
2
content. Should the
actual value deviate by more than
1 % from the above range, imple-
ment steps from page 15 (possibly
replace the burner).
8.
After testing, press
d
.
9.
Enter actual values into the service
report.
Setting the max. output
Note
The max. output can be limited for
heating operation
. You can limit the output
via the modulation range.
1.
Start up boiler.
2.
Press both
K
and
F
simulta-
neously until 100 flashes on the
display, (equals 100 % of the rated
output) and
A
appears. On
weather-compensated control
units, the display additionally
shows "Max. output".
3.
With
a
/
b
select the required
value in % of rated output as max.
output.
4.
Confirm the set value with
d
.
5.
Record the settings for max. output
on the additional type plate
included with the technical docu-
mentation. Affix the type plate next
to the original type plate on top of
the boiler.
Note
The output can also be limited for
DHW loading. For this, change coding
address 6F in code 2.
Further details regarding the individual steps
(cont.)
16
Initial start-up, inspection, maintenance
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...