Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
80:1
With 5 seconds' time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
80:0
Without time delay
80:2
to
80:199
Time delay adjustable
from 10 to 995; 1 step =
5 s
81:1
Automatic summer/win-
ter changeover
81:0
Manual summer/winter
changeover
81:2
The application of the
radio clock module will be
recognised automatically
81:3
Accept time via LON
88 :0
Temperature display in
Celsius
88 :1
Temperature display in
Fahrenheit
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
flow temperature subject
to set value if the outside
temperature changes;
1 step = 10 min
91:0
*
1
No external operating
mode changeover via
external extension
91:1
External heating program
changeover applies to
heating circuit without
mixer
91:2
External heating program
changeover applies to
heating circuit with mixer
91:3
External heating program
changeover applies to
heating circuit without
mixer and heating circuit
with mixer
95:0
Without Vitocom 100
communication inter-
face
95:1
With Vitocom 100 com-
munication interface;
automatic recognition
Code 2
(cont.)
51
Coding
56
92
550
GB
*1
Only for weather-compensated control units.
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...