External operating mode changeover
The "External operating mode chan-
geover" function is connected via
external extension input
aVD
. With
coding address 91 you can select the
heating circuit to which the change-
over of operating mode should apply:
Coding
Changeover of operating mode affects:
91:0
No changeover
91:1
Heating circuit without mixer (A1)
91:2
Heating circuit with mixer (M2)
91:3
Heating circuit without mixer and heating
circuit with mixer
With coding address d5, you can
select in which direction the change-
over should be made for each heating
circuit:
Coding
Changeover of operating mode affects:
d5:0
Changeover towards "Constantly reduced"
or "Constant standby mode" (subject to
the selected set value)
d5:1
Changeover towards "Constant heating
mode"
You can select the duration of the
operating mode changeover with cod-
ing address F2.
Coding
Changeover of operating mode affects:
F2:0
No changeover of operating mode
F2:1 to
F2:12
Duration of the operating mode change-
over 1 to 12 hours
The changeover of operating mode
remains active as long as the contact
remains closed, but no less than the
default duration selected with coding
address F2.
Control functions
102
Function description
56
92
550
GB
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...