Check the boiler temperature sensor, cylinder temperature
sensor or the flow temperature sensor for low loss header
1.
Boiler temperature sensor: Pull the
leads from boiler temperature
sensor
A
and measure the resis-
tance.
Cylinder temperature sensor: Pull
the plug
%
from the cable harness
on the control unit and measure the
resistance.
Flow temperature sensor: Pull
plug X3 from the control unit and
measure the resistance across
terminals X3.4 and X3.5.
Repairs
(cont.)
87
Troubleshooting
56
92
550
GB