Displayed
fault code
Const.
Weat-
her-
comp.
System
character-
istics
Cause
Remedy
F4
X
X
Burner in
fault state
No flame signal is
present
Check the
ionisation
electrode and
leads, mea-
sure the ioni-
sation cur-
rent, check
the gas pres-
sure, check
the gas com-
bination
valve, igni-
tion, ignition
module, igni-
tion electro-
des and the
condensate
drain.
Press
E
.
F7
X
X
Burner
blocked
Differential pres-
sure sensor faulty
Check the dif-
ferential pres-
sure sensor
and lead.
F8
X
X
Burner in
fault state
Fuel valve closes
too late
Check gas
combination
valve. Check
both control
paths.
Press
E
.
F9
X
X
Burner in
fault state
Fan speed too low
at burner start
Check the
fan, check the
fan cables
and supply,
check the fan
control.
Press
E
.