Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
E9:45
*
1
Speed of the variable
speed pump = 45 % of
max. speed in reduced
mode
E9:0
to
E9:100
Speed adjustable from 0
to 100 % of max. speed
Mixer circuit
F1:0
Screed drying function
disabled
*
1
F1:1
to
F1:5
Screed drying function
adjustable in accordance
with 5 optional tempera-
ture time profiles (see
page 104)
Note
Observe the screed dry-
ing supplier's instruc-
tions.
Observe DIN 4725-2 or
local regulations. The
report to be provided by
the heating contractor
must contain the follow-
ing heat-up details:
&
Heat-up data with
respective flow tem-
peratures
&
Max. flow temperature
achieved
&
Operating condition
and outside tempera-
ture during handover.
The function continues
after power failure or
after the control unit has
been switched OFF. The
heating program
rw
will be started, after the
Code 2
(cont.)
60
Coding
56
92
550
GB
*1
Only for weather-compensated control units.
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...