Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
b5:0
*
1
With remote control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
tion
*
2
b5:1
to
b5:8
Heating circuit pump
logic function - see the
following table
Parameter
address b5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
1:
active RT
Actual
> RT
Set
+ 5 K; passive RT
Actual
< RT
Set
+ 4 K
2:
active RT
Actual
> RT
Set
+ 4 K; passive RT
Actual
< RT
Set
+ 3 K
3:
active RT
Actual
> RT
Set
+ 3 K; passive RT
Actual
< RT
Set
+ 2 K
4:
active RT
Actual
> RT
Set
+ 2 K; passive RT
Actual
< RT
Set
+ 1 K
5:
active RT
Actual
> RT
Set
+ 1 K; passive RT
Actual
< RT
Set
6:
active RT
Actual
> RT
Set
; passive RT
Actual
< RT
Set
- 1 K
7:
active RT
Actual
> RT
Set
- 1 K; passive RT
Actual
< RT
Set
- 2 K
8:
active RT
Actual
> RT
Set
- 2 K; passive RT
Actual
< RT
Set
- 3 K
Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
Boiler circuit, mixer circuit
C5:20
*
1
Electronic limit of the
minimum flow tempera-
ture: 20 °C
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C
C6:74
*
1
Electronic limit of the
maximum flow tempera-
ture: 74 °C
C6:0
to
C6:127
Maximum limit adjustable
from 1 to 127 °C
d3:14
*
1
Heating curve slope =
1.4
d3:2
to
Heating curve slope
adjustable from 0.2 to 3.5
Code 2
(cont.)
58
Coding
56
92
550
GB
*1
Only for weather-compensated control units.
*2
Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
Summary of Contents for VITODENS 300 WB3A
Page 10: ...Opening the control unit housing 10 5862 570 GB...
Page 14: ...Closing control unit housing and inserting user interface 14 5862 570 GB...
Page 129: ...Parts lists cont 113 Parts lists 5692 550 GB...
Page 130: ...Parts lists cont 114 Parts lists 5692 550 GB...
Page 131: ...Parts lists cont 115 Parts lists 5692 550 GB...
Page 132: ...Parts lists cont 116 Parts lists 5692 550 GB...
Page 133: ...Parts lists cont 117 Parts lists 5692 550 GB...
Page 145: ...129 5692 550 GB...
Page 146: ...130 5692 550 GB...
Page 147: ...131 5692 550 GB...