146
CG Drives & Automation, 01-5326-01r3b
Rotor locked [422]
With the rotor locked function enabled, the AC drive will
protect the motor and application when this is stalled whilst
increasing the motor speed from standstill. This protection
will coast the motor to stop and indicate a fault when the
Torque Limit has been active at very low speed for more
than 5 seconds.
Communication information
Motor lost [423]
With the motor lost function enabled, the AC drive is able
to detect a fault in the motor circuit: motor, motor cable,
thermal relay or output filter. Motor lost will cause a trip,
and the motor will coast to standstill, when a missing motor
phase is detected during a period of 500 ms. The detection
time during DC-start is 50 ms and during Fast-start 10 ms. .
Communication information
Overvolt control [424]
Used to switch off the overvoltage control function when
only braking by brake chopper and resistor is required. The
overvoltage control function, limits the braking torque so
that the DC link voltage level is controlled at a high, but
safe, level. This is achieved by limiting the actual
deceleration rate during stopping. In case of a defect at the
brake chopper or the brake resistor the AC drive will trip for
“Overvoltage” to avoid a fall of the load e.g. in crane
applications.
Communication information
Default:
Off
Off
0
No detection
On
1
AC drive will trip when locked rotor is
detected. Trip message “Locked Rotor”.
Modbus Instance no/DeviceNet no:
43362
Profibus slot/index
170/11
EtherCAT index (hex)
4d22
Profinet IO index
19746
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
Function switched off to be used if no
motor or very small motor connected.
Trip
1
AC drive will trip when the motor is
disconnected. Trip message “Motor Lost”.
Start
2
Test for disconnected motor will only be
performed during start routine.
Modbus Instance no/DeviceNet no:
43363
Profibus slot/index
170/12
EtherCAT index (hex)
4d23
Profinet IO index
19747
Fieldbus format
UInt
Modbus format
UInt
422 Rotor locked
Stp
Off
423 Motor lost
Stp
Off
NOTE: Overvoltage control should not be activated if
brake chopper is used.
Default:
On
On
0
Overvoltage control activated
Off
1
Overvoltage control off
Modbus Instance no/DeviceNet no:
43364
Profibus slot/index
170/13
EtherCAT index (hex)
4d24
Profinet IO index
19748
Fieldbus format
UInt
Modbus format
UInt
424 Over Volt Ctl
Stp
On
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...