102
Functional Description
CG Drives & Automation, 01-5326-01r3b
Read/Write [2633]
Select read/write to control the inverter over a fieldbus
network. For further information, see the Fieldbus option
manual.
Communication information
Additional Process Values [2634]
Define the number of additional process values sent in cyclic
messages.
Communication information
Communication Fault [264]
Main menu for communication fault/warning settings. For
further details please see the Fieldbus option manual.
Communication Fault Mode [2641]]
Selects action if a communication fault is detected.
Communication information
Default:
RW
RW
0
Read
1
Valid for process data. Select R (read only) for logging
process without writing process data. Select RW in normal
cases to control inverter.
Modbus Instance no/DeviceNet no:
43036
Profibus slot/index
168/195
EtherCAT index (hex)
4bdc
Profinet IO index
19420
Fieldbus format
UInt
Modbus format
UInt
Default:
0
Range:
0-8
Modbus Instance no/DeviceNet no:
43039
Profibus slot/index
168/198
EtherCAT index (hex)
4bdf
Profinet IO index
19423
Fieldbus format
UInt, 1=1
Modbus format
UInt
2633 Read/Write
Stp
RW
2634 AddPrValues
Stp
0
Default:
Off
Off
0
No communication supervision.
Trip
1
RS232/485 selected:
The AC drive will trip if there is no
communication for time set in parameter
[2642].
Fieldbus selected:
The AC drive will trip if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
Warning
2
RS232/485 selected:
The AC drive will give a warning if there is
no communication for time set in
parameter [2642].
Fieldbus selected:
The AC drive will give a warning if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
NOTE: Menu [214] and/or [215] must be set to COM to
activate the communication fault function.
Modbus Instance no/DeviceNet no:
43037
Profibus slot/index
168/196
EtherCAT index (hex)
4bdd
Profinet IO index
19421
Fieldbus format
UInt
Modbus format
UInt
2641 ComFlt Mode
Stp
Off
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...