108
Functional Description
CG Drives & Automation, 01-5326-01r3b
Ratio [326]
This menu is not visible when speed, frequency or torque is
selected. The function sets the ratio between the actual
process value and the motor speed so that it has an accurate
process value when no feedback signal is used. See Fig. 80.
Communication information
Fig. 80 Ratio
F(Value), Process Min [327]
This function is used for scaling if no sensor is used. It offers
you the possibility of increasing the process accuracy by
scaling the process values. The process values are scaled by
linking them to known data in the AC drive. With
“F(Value) Proc Min [327]” the precise value at which the
entered “Process Min [324]“ is valid can be entered.
Communication information
F(Value), Process Max [328]
This function is used for scaling if no sensor is used. It offers
you the possibility of increasing the process accuracy by
scaling the process values. The process values are scaled by
linking them to known data in the AC drive. With F(Value),
Proc Max the precise value at which the entered “Process
Max [525]” is valid can be entered.
Default:
Linear
Linear
0
Process is linear related to speed/torque
Quadratic 1
Process is quadratic related to speed/
torque
Modbus Instance no/DeviceNet no:
43312
Profibus slot/index
169/216
EtherCAT index (hex)
4cf0
Profinet IO index
19696
Fieldbus format
UInt
Modbus format
UInt
326 Ratio
Stp
Linear
Ratio=Linear
Ratio=Quadratic
Process
Process
Process
Min Max
unit
Max
[325]
Min
[324]
Speed
[341]
Speed
Speed
[343]
NOTE: If Speed, Torque or Frequency is chosen in menu
“[321] Proc Source”, menus [322]- [328] are hidden.
Default:
Min
Min
-1
According to Min Speed setting in
[341].
Max
-2
According to Max Speed setting in
[343].
0.000-10000 0-10000 0.000-10000
Modbus Instance no/DeviceNet no:
43313
Profibus slot/index
169/217
EtherCAT index (hex)
4cf1
Profinet IO index
19697
Fieldbus format
Long, 1=1 rpm,
1 %
Modbus format
EInt
NOTE: If Speed, Torque or Frequency is chosen in menu
“[321] Proc Source”, menus [322]- [328] are hidden.
Default:
Max
Min
-1
Min
Max
-2
Max
0.000-
10000
0-10000 0.000-10000
327 F(Val) PrMin
Stp
Min
328 F(Val) PrMax
Stp
Max
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...