132
Functional Description
CG Drives & Automation, 01-5326-01r3b
Upper Band [397]
If the speed of the master drive comes into the upper band,
an additional drive will be added after a delay time that is set
in “Start delay [399]”.
Communication information
Example:
Max Speed = 1500 rpm
Min Speed = 300 rpm
Upper Band = 10%
Start delay will be activated:
Range = Max Speed to Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 1500–120 = 1380 rpm
Fig. 99 Upper band
Lower Band [398]
If the speed of the master drive comes into the lower band
an additional drive will be stopped after a delay time. This
delay time is set in the parameter “Stop Delay [39A]”.
Communication information
Example:
Max Speed = 1500 rpm
Min Speed = 300 rpm
Lower Band = 10%
Stop delay will be activated:
Range = Max Speed - Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 300 + 120 = 420 rpm
Fig. 100 Lower band
Start Delay [399]
This delay time must have elapsed before the next pump is
started. A delay time prevents the nervous switching of
pumps.
Communication information
Default:
10%
Range:
0-100% of total min speed to max speed
Modbus Instance no/DeviceNet no:
43167
Profibus slot/index
169/71
EtherCAT index (hex)
4c5f
Profinet IO index
19551
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
10%
Range:
0-100% of total min speed to max speed
397 Upper Band
Stp
10%
(NG_50-PC-12_1)
Flow/Pressure
Speed
Max
Min
Upper band
next pump starts
Start Delay [399]
398 Lower Band
Stp
10%
Modbus Instance no/DeviceNet no:
43168
Profibus slot/index
169/72
EtherCAT index (hex)
4c60
Profinet IO index
19552
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
0 s
Range:
0-999 s
Modbus Instance no/DeviceNet no:
43169
Profibus slot/index
169/73
EtherCAT index (hex)
4c61
Profinet IO index
19553
Fieldbus format
Long, 1=1s
Modbus format
EInt
(NG_50-PC-13_1)
Speed
Max
Min
“top” pump stops
Lower band
Stop Delay [39A]
Flow/Pressure
399 Start Delay
Stp
0s
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...