FFunctional Description
121
11.3.6 Torques [350]
Menu with all parameters for torque settings.
Maximum Torque [351]
Sets the maximum motor torque (according to menu group
“Motor Data [220]”). This Maximum Torque operates as an
upper torque limit. A Speed Reference is always necessary to
run the motor.
Communication information
IxR Compensation [352]
This function compensates for the drop in voltage over
different resistances such as (very) long motor cables, chokes
and motor stator by increasing the output voltage at a
constant frequency. IxR Compensation is most important at
low frequencies and is used to obtain a higher starting
torque. The maximum voltage increase is 25% of the
nominal output voltage. See Fig. 92.
Selecting “Automatic” will use the optimal value according
to the internal model of motor. “User-Defined” can be
selected when the start conditions of the application do not
change and a high starting torque is always required. A fixed
IxR Compensation value can be set in the menu [353].
Communication information
Fig. 92 IxR Comp at Linear V/Hz curve
IxR Comp_user [353]
Only visible if User-Defined is selected in previous menu.
Communication information
Default:
120% calculated from the motor data
Range:
0–400%
Modbus Instance no/DeviceNet no:
43141
Profibus slot/index
169/45
EtherCAT index (hex)
4c45
Profinet IO index
19525
Fieldbus format
Long, 1=1%
Modbus format
EInt
NOTE: The Max Torque parameter will limit the maxmum
output current of the AC drive following the relation:
100% Tmot corresponds to 100% Imot.
The maximum possible setting for parameter 351 is
limited by Inom/Imot x 120%, but not higher than 400%.
NOTE: The power loss in the motor will increase by the
square of the torque when operating above 100%. 400%
torque will result in 1600% power loss, which will
increase the motor temperature very quickly.
NOTE: This menu is visible only in V/Hz mode.
T
MOT
Nm
(
)
P
MOT
kw
(
)
x9550
n
MOT
rpm
(
)
------------------------------------------
=
= 100%
351 Max Torque
Stp
120%
Default:
Off
Off
0
Function disabled
Automatic
1
Automatic compensation
User Defined 2
User defined value in percent.
Modbus Instance no/DeviceNet no:
43142
Profibus slot/index
169/46
EtherCAT index (hex)
4c46
Profinet IO index
19526
Fieldbus format
UInt
Modbus format
UInt
Default:
0.0%
Range:
0-25% x U
NOM
(0.1% of resolution)
Modbus Instance no/DeviceNet no:
43143
Profibus slot/index
169/47
EtherCAT index (hex)
4c47
Profinet IO index
19527
Fieldbus format
Long, 1= 0.1 %
Modbus format
EInt
352 IxR Comp
Stp
Off
10
20
30
40
50 Hz
f
25
%
U
100
IxR Comp=25%
IxR Com=0%
353 IxR CompUsr
Stp
0.0%
9(0R'ULYH 96, 9(0 U
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...