CG Drives & Automation, 01-5326-01r3b
189
See also the Chapter 12. page 197.
Digital Input Status [723]
Indicates the status of the digital inputs. See Fig. 126.
1
DigIn 1
2
DigIn 2
3
DigIn 3
4
DigIn 4
5
DigIn 5
6
DigIn 6
7
DigIn 7
8
DigIn 8
The positions one to eight (read from left to right) indicate
the status of the associated input:
1
High
0
Low
The example in Fig. 126 indicates that DigIn 1,
DigIn 3 and DigIn 6 are active at this moment.
Fig. 126 Digital input status example
Communication information
Digital Output Status [724]
Indicates the status of the digital outputs and relays. See Fig.
127.
RE indicate the status of the relays on position:
1 Relay1
2 Relay2
3 Relay3
DO indicate the status of the digital outputs on position:
1 DigOut1
2 DigOut2
The status of the associated output is shown.
1 High
0 Low
The example in Fig. 127 indicates that DigOut1 is active
and Digital Out 2
is not active.
Relay 1 is active, relay 2 and
3 are not active.
Fig. 127 Digital output status example
Communication information
Analogue Input Status [725]
Indicates the status of the analogue inputs 1 and 2.
Fig. 128 Analogue input status
Communication information
The first row indicates the analogue inputs.
1
AnIn 1
2
AnIn 2
Reading downwards from the first row to the second row the
status of the belonging input is shown in %:
-100% AnIn1 has a negative 100% input value
65%
AnIn2 has a 65% input value
So the example in Fig. 128 indicates that both the Analogue
inputs are active.
Modbus Instance no/DeviceNet no:
31017
Profibus slot/index
121/161
EtherCAT index (hex)
23f9
Profinet IO index
1017
Fieldbus format
UInt,
bit 0=DigIn1,
bit 8=DigIn8
Modbus format
723 DigIn Status
Stp 1010
0100
Modbus Instance no/DeviceNet no:
31018
Profibus slot/index
121/162
EtherCAT index (hex)
23fa
Profinet IO index
1018
Fieldbus format
UInt,
bit 0=DigOut1,
bit 1=DigOut2
bit 8=Relay1
bit 9=Relay2
bit 10=Relay3
Modbus format
Modbus Instance no/DeviceNet no:
31019, 31020
Profibus slot/index
121/163, 121/164
EtherCAT index (hex)
23fb, 23fc
Profinet IO index
1019, 1020
Fieldbus format
Long, 1=1%
Modbus format
EInt
NOTE: The shown percentages are absolute values
based on the full range/scale of the in- or output; so
related to either 0–10 V or 0–20 mA.
724 DigOutStatus
Stp
RE 100 DO 10
725 AnIn 1
2
Stp
-100% 65%
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...