CG Drives & Automation,01-5326-01r3b
FFunctional Description
89
PT100 Inputs [236]
Sets which of PT100 inputs that should be used for thermal
protection. Deselecting not used PT100 inputs on the PTC/
PT100 option board in order to ignore those inputs, i.e.
extra external wiring is not needed if port is not used.
Communication information
Motor PTC [237]
For AC drive sizes B to D (
74*)%7"
)
optional possibility to directly connect motor PTC
be mixed up with PTC/PT100 option board, see
13.8 page 208).
In this menu the internal motor PTC hardware option is
enabled. This PTC input complies with DIN 44081/44082.
For electrical specification please refer to the separate
manual for the PTC/PT100 option board, same data applies
(could be found on www.
WFNHSPVQ
com).
This menu is only visible if a PTC (or resistor <2 kOhm) is
connected to terminals X1: 78–79. See Chapter 4.5 page 43
and Chapter 4.5.1 page 43.
To enable the function:
1. Connect the thermistor wires to X1: 78–79 or for testing
the input, connect a resistor to the terminals .Use resistor
value between 50 and 2000 ohm.
Menu [237] will now appear.
2. Enable input by setting menu “[237] Motor PTC”=On.
If enabled and <50 ohm a sensor error trip will occur. The
fault message “Motor PTC” is shown.
If the function is disabled and the PTC or resistor is
removed, the menu will disappear after the next power on
Communication information
Default:
PT100 1+2+3
Selection:
PT100 1, PT100 2, PT100 1+2, PT100
3, PT100 1+3, PT100 2+3, PT100
1+2+3
PT100 1
1
Channel 1 used for PT100 protection
PT100 2
2
Channel 2 used for PT100 protection
PT100 1+2
3
Channel 1+2 used for PT100 protection
PT100 3
4
Channel 3 used for PT100 protection
PT100 1+3
5
Channel 1+3 used for PT100 protection
PT100 2+3
6
Channel 2+3 used for PT100 protection
PT100 1+2+3 7
Channel 1+2+3 used for PT100
protection
Modbus Instance no/DeviceNet no:
43066
Profibus slot/index
168/225
EtherCAT index (hex)
4bfa
Profinet IO index
19450
Fieldbus format
UInt
Modbus format
UInt
NOTE: This menu is only valid for PT 100 thermal
protection if PT100 is enabled in menu [234].
236 PT100 Inputs
Stp
PT100 1+2+3
NOTE: This function is not related to PTC/PT100 option
board.
Default:
Off
Off
0
Motor PTC protection is disabled
On
1
Motor PTC protection is enabled
Modbus Instance no/DeviceNet no:
43067
Profibus slot/index
168/226
EtherCAT index (hex)
4bfb
Profinet IO index
19451
Fieldbus format
UInt
Modbus format
UInt
237 Motor PTC
Stp
Off
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...