FFunctional Description
105
Communication information
11.3.2 Process Settings [320]
With these functions, the AC drive can be set up to fit the
application. The menus [110], [120], [310], [362]-[368]
and [711] use the process unit selected in [321] and [322]
for the application, e.g. rpm, bar or m3/h. This makes it
possible to easily set up the AC drive for the required process
requirements, as well as for copying the range of a feedback
sensor to set up the Process Value Minimum and Maximum
in order to establish accurate actual process information.
Process Source [321]
Select the signal source for the process value that controls
the motor. The Process Source can be set to act as a function
of the process signal on AnIn F(AnIn), a function of the
motor speed F(Speed), a function of the shaft torque
F(Torque) or as a function of a process value from serial
communication F(Bus). The right function to select
depends on the characteristics and behaviour of the process.
If the selection Speed, Torque or Frequency is set, the AC
drive will use speed, torque or frequency as reference value.
Example
An axial fan is speed-controlled and there is no feedback
signal available. The process needs to be controlled within
fixed process values in “m
3
/hr” and a process read-out of the
air flow is needed. The characteristic of this fan is that the air
flow is linearly related to the actual speed. So by selecting
F(Speed) as the Process Source, the process can easily be
controlled.
The selection F(xx) indicates that a process unit and scaling
is needed, set in menus [322]-[328]. This makes it possible
to e.g. use pressure sensors to measure flow etc. If F(AnIn) is
selected, the source is automatically connected to the AnIn
which has Process Value as selected.
1
. Only when Drive mode [213] is set to Speed or V/Hz.
2
. Only when Drive mode [213] is set to Torque.
Communication information
Modbus Instance no/DeviceNet no:
42991
Profibus slot/index
168/150
EtherCAT index (hex)
4baf
Profinet IO index
19375
Fieldbus format
Long, 1=1 rpm,
1 %,1 °C or
0.001 if Process
Value/Process Ref
using a [322] unit
Modbus format
EInt
NOTE: The actual value in menu [310] is not copied, or
loaded from the control panel memory when Copy Set
[242], Copy to CP [244] or Load from CP [245] is
performed.
NOTE: If the MotPot function is used, the reference value
ramp times are according to the “Acc MotPot [333]” and
“Dec MotPot [334]” settings. Actual speed ramp will be
limited according to “Acc Time [331]” and
“Dec Time [332]”.
NOTE: Write access to this parameter is only allowed
when menu “Ref Control [214]” is set to Keyboard. When
Reference control is used, see section “10. Serial
communication” on page 69
Default:
Speed
F(AnIn)
0
Function of analogue input. E.g. via PID
control, [380].
Speed
1
Speed as process reference
1
.
Torque
2
Torque as process reference
2
.
PT100
3
Temperature as process reference.
F(Speed)
4
Function of speed
F(Torque)
5
Function of torque
2
F(Bus)
6
Function of communication reference
Frequency 7
Frequency as process reference
1
.
NOTE: When PT100 is selected, use PT100 channel 1 on
the PTC/PT100 option board.
NOTE: If Speed, Torque
or Frequency is chosen in menu
“[321] Proc Source”, menus [322] - [328] are hidden.
NOTE: The motor control method depends on the
selection of drive mode [213], regardless of selected
process source, [321].
NOTE: If F (Bus) is chosen in menu [321] see “11.5.1
Analogue Inputs [510]” on page 147.
Modbus Instance no/DeviceNet no:
43302
Profibus slot/index
169/206
EtherCAT index (hex)
4ce6
Profinet IO index
19686
Fieldbus format
UInt
Modbus format
UInt
321 Proc Source
Stp
Speed
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...