136
Functional Description
CG Drives & Automation, 01-5326-01r3b
Run Times 1-6 [39H] to [39M]
Communication information
Reset Run Times 1-6 [39H1] to [39M1]
Communication information
Pump Status [39N]
Communication information
Number backup/reserve [39P]
Sets the number of pumps used for backup/reserve which in
normal conditions can not be selected. This function can be
used for increasing redundancy in the pump system by
having pumps in reserve that can be activated when some
pumps indicate fault or are shut off for maintenance.
Communication information
Unit:
h:mm:ss (hours:minutes:seconds)
Range:
0:00:00–262143:59:59
Modbus Instance no/
DeviceNet no:
31051 : 31052 : 31053(hr:min:sec)
31054 : 31055: 31056(hr:min:sec)
31057 : 31058: 31059(hr:min:sec)
31060 : 31061: 31062(hr:min:sec)
31063 : 31064: 31065(hr:min:sec)
31066 : 31067: 31068(hr:min:sec)
Profibus slot/index
121/195, 121/196, 121/197,
121/198, 121/199, 121/200,
121/201, 121/202, 121/203,
121/204, 121/205, 121/206,
121/207, 121/208, 121/209,
121/210, 121/211, 121/212
EtherCAT index (hex)
241b : 241c : 241d
241e : 241f : 2420
2421 : 2422 : 2423
2424 : 2425 : 2426
2427 : 2428 : 2429
242a : 242b : 242c
Profinet IO index
1051:1052:1053
- 1068
Fieldbus format
Long, 1=1h/m/s
Modbus format
EInt
Default:
No
No
0
Yes
1
Modbus Instance no/DeviceNet no:
38–43, pump 1 -6
Profibus slot/index
0/37–0/42
EtherCAT index (hex)
2026 - 202b
Profinet IO index
38 - 43
Fieldbus format
UInt
Modbus format
UInt
39H Run Time 1
Stp
h:mm:ss
39H1 Rst Run Tm1
Stp
No
Indication
Description
C
Control, master pump, only when alternating
master is used
D
Direct control
O
Pump is off
E
Pump error
Modbus Instance no/DeviceNet no:
31069
Profibus slot/index
121/213
EtherCAT index (hex)
242d
Profinet IO index
1069
Fieldbus format
UInt
Modbus format
UInt
Default:
0
Range:
0-3
Modbus Instance no/DeviceNet no:
43177
Profibus slot/index
169/81
EtherCAT index (hex)
4c69
Profinet IO index
19561
Fieldbus format
UInt
Modbus format
UInt
39N Pump 123456
Stp
--OCD-
39P No of Backup
Stp
0
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...