CG Drives & Automation, 01-5326-01r3b
Additional digital inputs [529] to [52H]
Additional digital inputs with I/O option board installed,
“B1 DigIn 1 [529]” - “B3 DigIn 3 [52H]”. B stands for
board and 1 to 3 is the number of the board which is related
to the position of the I/O option board on the option
mounting plate. The functions and selections are the same as
“DigIn 1 [521]”.
Communication information
11.5.3 Analogue Outputs [530]
Submenu with all settings for the analogue outputs.
Selections can be made from application and AC drive
values, in order to visualize actual status. Analogue outputs
can also be used as a mirror of the analogue input. Such a
signal can be used as:
•
a reference signal for the next AC drive in a Master/Slave
configuration (see Fig. 114
QBHF
).
•
a feedback acknowledgement of the received analogue
reference value.
AnOut1 Function [531]
Sets the function for the Analogue Output 1. Scale and
range are defined by AnOut1 Advanced settings [533].
Modbus Instance no/DeviceNet no:
43501–43509
Profibus slot/index
170/150–170/158
EtherCAT index (hex)
4dad - 4db5
Profinet IO index
19885 - 19893
Fieldbus format
UInt
Modbus format
UInt
Default:
Speed
Process Val 0
Actual process value according to
Process feedback signal.
Speed
1
Actual speed.
Torque 2
Actual
torque.
Process Ref 3
Actual process reference value.
Shaft Power 4
Actual shaft power.
Frequency
5
Actual frequency.
Current
6
Actual current.
El power
7
Actual electrical power.
Output volt
8
Actual output voltage.
DC-voltage
9
Actual DC link voltage.
AnIn1
10
Mirror of received signal value on
AnIn1.
AnIn2
11
Mirror of received signal value on
AnIn2.
AnIn3
12
Mirror of received signal value on
AnIn3.
AnIn4
13
Mirror of received signal value on
AnIn4.
Speed Ref
14
Actual internal speed reference Value
after ramp and V/Hz.
Torque Ref
15
Actual torque reference value
(=0 in V/Hz mode)
NOTE: When selections AnIn1, AnIn2 …. AnIn4 is
selected, the setup of the AnOut (menu [532] or [535])
has to be set to 0-10V or 0-20mA. When the AnOut Setup
is set to e.g. 4-20mA, the mirroring is not working
correct.
531 AnOut1 Fc
Stp
Speed
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...