![VEM VEMoDRIVE VSI 2.0 HD Instruction Manual Download Page 166](http://html1.mh-extra.com/html/vem/vemodrive-vsi-2-0-hd/vemodrive-vsi-2-0-hd_instruction-manual_3985886166.webp)
164
CG Drives & Automation, 01-5326-01r3b
11.5.6 Virtual Connections [560]
Functions to enable eight internal connections of
comparator, timer and digital signals, without occupying
physical digital in/outputs. Virtual connections are used to
wireless connection of a digital output function to a digital
input function. Available signals and control functions can
be used to create your own specific functions.
Example of start delay
The motor will start in RunR 10 seconds after DigIn1 gets
high. DigIn1 has a time delay of 10 s.
Virtual Connection 1 Destination [561]
With this function the destination of the virtual connection
is established. When a function can be controlled by several
sources, e.g. VC destination or Digital Input, the function
will be controlled in conformity with “OR logic”. See DigIn
for descriptions of the different selections.
Communication information
Virtual Connection 1 Source [562]
With this function the source of the virtual connection is
defined. See DigOut 1 for description of the different
selections.
Communication information
Virtual Connections 2-8 [563] to [56G]
Same function as virtual connection 1 [561] and [562].
Communication information for virtual connections 2-8
Destination.
Communication information for virtual connections 2-8
Source.
Menu
Parameter
Setting
[521]
DigIn1
Timer 1
[561]
VIO 1 Dest
RunR
[562]
VIO 1 Source
T1Q
[641]
Timer1 Trig
DigIn 1
[642]
Timer1 Mode
Delay
[643]
Timer1 Delay
0:00:10
NOTE: When a digital input and a virtual destination are
set to the same function, this function will act as an OR
logic function.
Default:
Off
Selection:
Same selections as for Digital Input 1,
menu [521].
Modbus Instance no/DeviceNet no:
43281
Profibus slot/index
169/185
EtherCAT index (hex)
4cd1
Profinet IO index
19665
Fieldbus format
UInt
Modbus format
UInt
561 VIO 1 Dest
Stp
Off
Default:
Off
Selection:
Same as for menu [541].
Modbus Instance no/DeviceNet no:
43282
Profibus slot/index
169/186
EtherCAT index (hex)
4cd2
Profinet IO index
19666
Fieldbus format
UInt
Modbus format
UInt
Modbus Instance no/DeviceNet no:
43283, 43285, 43287,
43289, 43291, 43293,
43295
Profibus slot/index
169/ 187, 189, 191, 193,
195, 197, 199
EtherCAT index (hex)
4cd3, 4cd5, 4cd17, 4cd9,
4cdb, 4cdd, 4cdf
Profinet IO index
19667, 19669, 19671,
19673, 19675, 19677,
19679
Fieldbus format
UInt
Modbus format
UInt
Modbus Instance no/DeviceNet no:
43284, 43286, 43288,
43290, 43292, 43294,
43296
Profibus slot/index
169/ 188, 190, 192, 194,
196, 198, 200
EtherCAT index (hex)
4cd4, 4cd6, 4cd8, 4cda,
4cdc, 4cde, 4ce0
Profinet IO index
19668, 19670, 19672,
19674, 19676, 19678,
19680
Fieldbus format
UInt
Modbus format
UInt
562 VIO 1 Source
Stp
Off
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...