Functional Description
CG Drives & Automation, 01-5326-01r3b
11.3.9 PID Process Control [380]
The PID controller is used to control an external process via
a feedback signal. The reference value can be set via analogue
input AnIn1, at the Control Panel [310] by using a Preset
Reference, or via serial communication. The feedback signal
(actual value) must be connected to an analogue input that
is set to the function Process Value.
Process PID Control [381]
This function enables the PID controller and defines the
response to a changed feedback signal.
Communication information
PID P Gain [383]
Setting the P gain for the PID controller.
Communication information
Fig. 95 Closed loop PID control
PID I Time [384]
Setting the integration time for the PID controller.
Communication information
Process PID D Time [385]
Setting the differentiation time for the PID controller.
Communication information
Default:
Off
Off
0
PID control deactivated.
On
1
The speed increases when the feedback
value decreases. PID settings according to
menus [381] to [385].
Invert
2
The speed decreases when the feedback
value decreases. PID settings according to
menus [383] to [385].
Modbus Instance no/DeviceNet no:
43154
Profibus slot/index
169/58
EtherCAT index (hex)
4c52
Profinet IO index
19538
Fieldbus format
UInt
Modbus format
UInt
Default:
1.0
Range:
0.0–30.0
Modbus Instance no/DeviceNet no:
43156
Profibus slot/index
169/60
EtherCAT index (hex)
4c54
Profinet IO index
19540
Fieldbus format
Long, 1=0.1
Modbus format
EInt
381 PID Control
Stp
Off
383 PID P Gain
Stp
1.0
Default:
1.00 s
Range:
0.01–300 s
Modbus Instance no/DeviceNet no:
43157
Profibus slot/index
169/61
EtherCAT index (hex)
4c55
Profinet IO index
19541
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
Default:
0.00 s
Range:
0.00–30 s
Modbus Instance no/DeviceNet no:
43158
Profibus slot/index
169/62
EtherCAT index (hex)
4c56
Profinet IO index
19542
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
+
M
-
06-F95
Process
reference
Process
feedback
Process
PID
AC drive
Process
384 PID I Time
Stp
1.00s
385 PID D Time
Stp
0.00s
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...