CG Drives & Automation,01-5326-01r3b
FFunctional Description
113
Communication information
Spinstart [33A]
The spinstart will smoothly start a motor which is already
rotating by catching the motor at the actual speed and
control it to the desired speed. If in an application, such as
an exhausting fan, the motor shaft is already rotating due to
external conditions, a smooth start of the application is
required to prevent excessive wear. With the spinstart=On,
the actual control of the motor is delayed due to detecting
the actual speed and rotation direction, which depend on
motor size, running conditions of the motor before the
Spinstart, inertia of the application, etc. Depending on the
motor electrical time constant and the size of the motor, it
can take maximum a couple of minutes before the motor is
caught.
Communication information
Stop Mode [33B]
When the AC drive is stopped, different methods to come to
a standstill can be selected in order to optimize the stop and
prevent unnecessary wear. Stop Mode sets the way of
stopping the motor when a Stop command is given.
Communication information
Modbus Instance no/DeviceNet no:
43109
Profibus slot/index
169/13
EtherCAT index (hex)
4c25
Profinet IO index
19493
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
No spinstart. If the motor is already running
the AC drive can trip or will start with high
current.
On
1
Spinstart will allow the start of a running
motor without tripping or high inrush currents.
If encoder feedback is used, both encoder
speed and current signals are used to
perform spinstart function.
Encoder 2
Only encoder speed used for detecting
rotating machine, i.e. no rotating machine
detection via initial motor current.
Note: Only active if encoder is present. If no
Encoder, functionality is equal to selection
Off.
Modbus Instance no/DeviceNet no:
43110
Profibus slot/index
169/14
EtherCAT index (hex)
4c26
Profinet IO index
19494
Fieldbus format
UInt
Modbus format
UInt
33A Spinstart
Stp
Off
Default:
Decel
Decel
0
The motor decelerates to 0 rpm according
to the set deceleration time.
Coast
1
The motor freewheels naturally to 0 rpm.
Modbus Instance no/DeviceNet no:
43111
Profibus slot/index
169/15
EtherCAT index (hex)
4c27
Profinet IO index
19495
Fieldbus format
UInt
Modbus format
UInt
33B Stop Mode
Stp
Decel
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...