154
CG Drives & Automation, 01-5326-01r3b
AnIn4 Set-up [51B]
Same functions as “AnIn1 Setup [512]”.
Communication information
AnIn4 Advanced [51C]
Same functions and submenus as under “AnIn1
Advan[513]”.
Communication information
11.5.2 Digital Inputs [520]
Submenu with all the settings for the digital inputs.
Digital Input 1 [521]
To select the function of the digital input.
On the standard control board there are eight digital inputs.
If the same function is programmed for more than one input
that function will be activated according to “OR” logic if
nothing else is stated.
Default:
4-20 mA
Dependent on
Setting of switch S4
Selection:
Same as in menu
[
512
].
Modbus Instance no/DeviceNet no:
43232
Profibus slot/index
169/136
EtherCAT index (hex)
4ca0
Profinet IO index
19616
Fieldbus format
UInt
Modbus format
UInt
Modbus Instance no/DeviceNet no:
43233–43240,
43544,
43554
Profibus slot/index
169/137–144,
170/193,
170/203
EtherCAT index (hex)
4ca1 - 4ca8,
4dd8,
4de2
Profinet IO index
19617-19624,
19928,
19938
Fieldbus format
See [5131] - [5137].
Modbus format
51B AnIn4 Setup
Stp
4-20mA
51C AnIn4 Advan
Stp
NOTE: Additional inputs will become available when the
I/O option boards are connected.
Default:
RunL
Off
0
The input is not active.
Lim 1
AC drive ramps to stop and prevents
rotation in “R” direction (clockwise), when
the signal is low!
NOTE: The Lim is active low.
NOTE: Activated according to “AND” logic.
Lim Switch - 2
AC drive ramps to stop and prevents
rotation in “L” direction (counter clockwise)
when the signal is low!
NOTE: The Lim Switch- is active low.
NOTE: Activated according to “AND” logic.
Ext. Trip
3
Be aware that if there is nothing connected
to the input, the AC drive will trip at
“External trip” immediately.
NOTE: The External Trip is active low.
NOTE: Activated according to “AND” logic.
Stop
4
Stop command according to the selected
Stop mode in menu [33B].
NOTE: The Stop command is active low.
NOTE: Activated according to “AND” logic.
Enable
5
Enable command. General start condition
to run the AC drive. If made low during
running the output of the AC drive is cut off
immediately, causing the motor to coast to
zero speed.
NOTE: If none of the digital inputs are
programmed to “Enable”, the internal
enable signal is active.
NOTE: Activated according to “AND” logic.
RunR
6
Run Right command (positive speed). The
output of the AC drive will be a
clockwise rotary field.
RunL
7
Run Left command (negative speed). The
output of the AC drive will be a
counter-clockwise rotary field.
Reset 9
Reset command. To reset a Trip condition
and to enable the Autoreset function.
Preset Ctrl1 10 To select the Preset Reference.
521 DigIn 1
Stp
RunL
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...