190
CG Drives & Automation, 01-5326-01r3b
Analogue Input Status [726]
Indicates the status of the analogue inputs 3 and 4.
Fig. 129 Analogue input status
Communication information
Analogue Output Status [727]
Indicates the status of the analogue outputs. Fig. 130. E.g. if
4-20 mA output is used, the value 20% equals to 4 mA.
Fig. 130 Analogue output status
Communication information
The first row indicates the Analogue outputs.
1 AnOut 1
2 AnOut 2
Reading downwards from the first row to the second row the
status of the belonging output is shown in %:
-100%AnOut1 has a negative 100% output value
65%AnOut2 has a 65% output value
The example in Fig. 130 indicates that both the Analogue
outputs are active.
I/O board Status [728] - [72A]
Indicates the status for the additional I/O on option boards
1 (B1), 2 (B2) and 3 (B3).
Communication information
Status bits [72B]
This menu is not visible in the control panel display. It is
used in
7&.P
SoftCom PC-tool (optional) and can be read
via fieldbus or serial communication, see Chapter 9.2.1 page
63.
Communication information
VIO Status[72C]
Shows the values of the 8 Virtual IO´s in menu[560]
Communication information
Modbus Instance no/DeviceNet no:
31021, 31022
Profibus slot/index
121/165, 121/166
EtherCAT index (hex)
23fd, 23fe
Profinet IO index
1021, 1022
Fieldbus format
Long, 1=1%
Modbus format
EInt
Modbus Instance no/DeviceNet no:
31023, 31024
Profibus slot/index
121/167, 121/168
EtherCAT index (hex)
23ff, 2400
Profinet IO index
1023, 1024
Fieldbus format
Long, 1=1%
Modbus format
EInt
NOTE: The shown percentages are absolute values
based on the full range/scale of the in- or output; so
related to either 0–10 V or 0–20 mA.
726 AnIn 3
4
Stp
-100% 65%
727 AnOut 1
2
Stp
-100% 65%
Modbus Instance no/DeviceNet no:
31025 - 31027
Profibus slot/index
121/170 - 172
EtherCAT index (hex)
2401 - 2403
Profinet IO index
1025 - 1027
Fieldbus format
UInt,
bit 0=DigIn1
bit 1=DigIn2
bit 2=DigIn3
bit 8=Relay1
bit 9=Relay2
bit 10=Relay3
Modbus format
Modbus Instance no/DeviceNet no:
30180
Profibus slot/index
118/89
EtherCAT index (hex)
20b4
Profinet IO index
180
Fieldbus format
UInt
Modbus format
UInt
Modbus Instance no/DeviceNet no:
30181
Profibus slot/index
118/90
EtherCAT index (hex)
20b5
Profinet IO index
181
Fieldbus format
UInt
Modbus format
UInt
728 IO B1
Stp
RE 000 DI100
72C VIO Status
Stp
00000000
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...