14.7 Control signals
Table 59
Terminal X1
Name:
Function (Default):
Signal:
Type:
1
+10 V
+10 VDC Supply voltage
+10 VDC, max 10 mA
output
2
AnIn1
Process reference
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
3
AnIn2
Off
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
4
AnIn3
Off
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
5
AnIn4
Off
0 -10 VDC or 0/4–20 mA
bipolar: -10 - +10 VDC or -20 - +20 mA
analogue input
6
-10 V
-10VDC Supply voltage
-10 VDC, max 10 mA
output
7
Common
Signal ground
0V
output
8
DigIn 1
RunL
0-8/24 VDC
digital input
9
DigIn 2
RunR
0-8/24 VDC
digital input
10
DigIn 3
Off
0-8/24 VDC
digital input
11
+24 V
+24VDC Supply voltage
+24 VDC, 100 mA
output
12
Common
Signal ground
0 V
output
13
AnOut 1
Min speed to max speed
0 ±10 VDC or 0/4– +20 mA
analogue output
14
AnOut 2
0 to max torque
0 ±10 VDC or 0/4– +20 mA
analogue output
15
Common
Signal ground
0 V
output
16
DigIn 4
Off
0-8/24 VDC
digital input
17
DigIn 5
Off
0-8/24 VDC
digital input
18
DigIn 6
Off
0-8/24 VDC
digital input
19
DigIn 7
Off
0-8/24 VDC
digital input
20
DigOut 1
Ready
24 VDC, 100 mA
digital output
21
DigOut 2
Brake
24 VDC, 100 mA
digital output
22
DigIn 8
RESET
0-8/24 VDC
digital input
Terminal X2
31
N/C 1
Relay 1 output
Trip, active when the
AC drive is in a TRIP condition
N/C is opened when the relay is active
(valid for all relays)
N/O is closed when the relay is active
(valid for all relays)
potential free change over
0.1 – 2 A
U
max
= 250 VAC or 42 VDC
relay output
32
COM 1
33
N/O 1
41
N/C 2
Relay 2 Output
Run, active when the
AC drive is started
potential free change over
0.1 – 2 A
U
max
= 250 VAC or 42 VDC
relay output
42
COM 2
43
N/O 2
Terminal X3
51
COM 3
Relay 3 Output
Off
potential free change over
0.1 – 2 A
U
max
= 250 VAC or 42 VDC
relay output
52
N/O 3
NOTE: Possible potentiometer value in range of 1 k
Ƙ
to 10 k
Ƙ
(¼ Watt) linear, where we advice to use a linear 1 k
Ƙ
/ ¼ W
type potentiometer for best control linearity.
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...