Functional Description
CG Drives & Automation, 01-5326-01r3b
Example 2 PID control = inverted (tank level
control)
[321] = F (AnIn)
[322] = m
[310] = 7 m
[342] = 2 s (inactive since [386] is activated and have higher
priority)
[381]= Inverted
[386] = 30 s
[387] = 1 m
The AC drive will stop/sleep when the speed (PID output) is
below or equal to Min Speed for 30 seconds. The AC drive
will activate/wake up when the “Process value” goes above
the PID Activation Margin which is related to the process
reference, i.e. goes above (7+1) m. See Fig. 97.
Fig. 97 PID Stop/sleep with inverted PID
PID Steady State Test [388]
In application situations where the feedback can become
independent of the motor speed, this PID Steady Test
function can be used to overrule the PID operation and
force the AC drive to go in sleep mode i.e. the AC drive
automatically reduces the output speed while at the same
time ensures the process value.
Example: pressure controlled pump systems with low/no
flow operation and where the process pressure has become
independent of the pump speed, e.g. due to slowly closed
valves. By going into Sleep mode, heating of the pump and
motor will be avoided and no energy is spilled.
PID Steady state test delay.
Communication information
PID Steady State Margin [389]
PID steady state margin defines a margin band around the
reference that defines “steady state operation”. During the
steady state test the PID operation is overruled and the AC
drive is decreasing the speed as long as the PID error is
within the steady state margin. If the PID error goes outside
the steady state margin the test failed and normal PID
operation continues, see example.
Communication information
NOTE: It is important that the system has reached a
stable situation before the Steady State Test is initiated.
Default:
Off
Range:
Off, 0.01–3600 s
[711] Process Value
[387]
[712] Speed
[341] Min Speed
[386]
Stop/Sleep
[310] Process Ref
Activate/Wake up
388 PID Stdy Tst
Stp
Off
Modbus Instance no/DeviceNet no:
43373
Profibus slot/index
170/22
EtherCAT index (hex)
4d2d
Profinet IO index
19757
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
Default:
0
Range:
0–10000 in process unit
Modbus Instance no/DeviceNet no:
43374
Profibus slot/index
170/23
EtherCAT index (hex)
4d2e
Profinet IO index
19758
Fieldbus format
Long, 1= 1 rpm, 1
%, 1°C or
0.001 if Process
Value/Process Ref
using a [322] unit
Modbus format
EInt
389 PID Stdy Mar
Stp
0
9(0R'ULYH 96, 9(0 U
Summary of Contents for VEMoDRIVE VSI 2.0 HD
Page 1: ...Frequency converter VEMoDRIVE VSI 2 0 HD Instruction manual 01 5326 01 04 2018...
Page 2: ......
Page 4: ......
Page 40: ...38 Installation CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 52: ...50 Getting Started CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 64: ...62 EMC and standards CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 142: ...140 Functional Description CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 198: ...196 CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 232: ...230 Technical Data CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 238: ...236 Menu List CG Drives Automation 01 5326 01r3b 9 0R ULYH 96 9 0 U...
Page 243: ...241 9 0R ULYH 96 9 0 U...