SIPART DR20
Project Planning Manual
1.
Press selector 8 until the two-digit display 6 outputs "PS" (flashing). Release push-button;
the display "PS" becomes steady.
The two digital displays no longer indicate any process variables. The controller is still fully
functional and indicates the negative deviation xd.
2.
Now press pushbutton 12.1 several times until the letters "PAr" appear in the four-digit
display. The controller can now be parameterized.
3.
Page through the parameter list forwards or backwards using pushbuttons 5.1 and 5.2. The
display 6 indicates the selected parameter.
4.
Set the selected parameter using pushbutton 12.1 or 12.2. Its value is indicated on the four-
digit display 4.
5.
Return to process mode by pressing pushbutton 8 once.
6.3 Configuring
(off-line)
The configuring switch list can be found in Table 3/1 on page 19.
To select and set the configuration, proceed in an analog manner to parameterization
1.
Press selector 8 until the two-digit display 6 outputs "PS" (flashing). Release push-button; the
display "PS" becomes steady.
2.
Now press pushbutton 12.1 until the four-digit display first indicates the letters "PAr" and then
"Str". The controller can now be configured.
The controller now blocks its output. Display 1 outputs a strip pattern.
3.
Page through the configuring switch list forwards or backwards using pushbutton 5.1 and 5.2.
The two-digit display now indicates the selected configuring switch.
4.
Set the selected configuring switch using pushbutton 12.1 or 12.2. The selected setting is
indicated on the four-digit display.
5.
Return by pressing pushbutton 8. The display first jumps to parameterization mode and then
to process operation mode if pushbutton 8 is pressed again.
The controller is now in absolute manual mode, i.e. the control signals N, BL, Si are only
effective after the automatic / manual key has been pressed once.
89