p3884
CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7033
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the setpoint for p3881 = 4 (technology controller) in the essential service mode (ESM).
Dependency:
See also: p3881
Note
ESM: Essential Service Mode
For p3884 = 0:
The technology controller uses the setpoint from p2253.
r3889.0...10
CO/BO: ESM status word / ESM ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7033
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the status word of the essential service mode (ESM).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Essential service mode (ESM) activated
Yes
No
-
01
Direction of rotation inverted
Yes
No
-
02
Setpoint signal lost
Yes
No
-
03
Technology controller actual value (p2264) lost
Yes
No
-
04
Bypass active
Yes
No
-
05
Setpoint technology controller parameterized (p3884)
Yes
No
-
06
Technology controller during essential service mode active Yes
No
-
09
Response OFF1/OFF2 activated
Yes
No
-
10
Automatic restart interrupted (F07320)
Yes
No
-
Note
ESM: Essential Service Mode
p3900
Completion of quick commissioning / Compl quick_comm
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
655