p0748
CU invert digital outputs / CU DO inv
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2201, 2242
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Setting to invert the signals at the digital outputs.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (NO: X134. 19 / NC: X134. 18)
Inverted
Not inverted
-
01
DO 1 (NO: X134. 21)
Inverted
Not inverted
-
02
DO 2 (NO: X134. 24)
Inverted
Not inverted
-
03
DO 3 (NO: X134. 51)
Inverted
Not inverted
-
Note
DO: Digital Output
Relay output: NO = normally open, NC = normally closed
r0751.0...11
BO: CU analog inputs status word / CU AI status word
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2251, 2252
Min:
-
Max:
-
Factory setting:
-
Description:
Display and binector output for the status of the analog inputs.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Analog input AI0 wire breakage
Yes
No
-
01
Analog input AI1 wire breakage
Yes
No
-
02
Analog input AI2 wire breakage
Yes
No
-
03
Analog input AI3 wire breakage
Yes
No
-
08
Analog input AI0 no wire breakage
Yes
No
-
09
Analog input AI1 no wire breakage
Yes
No
-
10
Analog input AI2 no wire breakage
Yes
No
-
11
Analog input AI3 no wire breakage
Yes
No
-
Note
AI: Analog Input
r0752[0...3]
CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p0514
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9566, 9568,
9576
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Displays the actual temperature in °C when set as temperature sensor and the voltage divider is switched in.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Parameters