p2127[0...19]
Change acknowledge mode mode / Chng ackn mode
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
1
Max:
2
Factory setting:
1
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
Acknowledgment only using POWER ON
2:
Ack IMMEDIATELY after the fault cause has been removed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
See also: p2126
NOTICE
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
p2128[0...15]
Faults/alarms trigger selection / F/A trigger sel
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8070
Min:
0
Max:
65535
Factory setting:
0
Description:
Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
See also: r2129
r2129.0...15
CO/BO: Faults/alarms trigger word / F/A trigger word
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8070
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the trigger signals of the faults/alarms set in p2128[0...15].
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Trigger signal p2128[0]
ON
OFF
-
01
Trigger signal p2128[1]
ON
OFF
-
02
Trigger signal p2128[2]
ON
OFF
-
03
Trigger signal p2128[3]
ON
OFF
-
04
Trigger signal p2128[4]
ON
OFF
-
05
Trigger signal p2128[5]
ON
OFF
-
06
Trigger signal p2128[6]
ON
OFF
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
584
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB