Note
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature inductance
Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
For bit 19 = 1:
All parameters are automatically saved after a successful motor data identification.
If a speed controller optimization run is then selected, the parameters are only saved after this measurement has been
completed.
For bit 21 = 1:
The converter output voltage measurement is calibrated at the start of the motor data identification.
p1910
Motor data identification selection / MotID selection
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
28
Factory setting:
0
Description:
Sets the motor data identification routine.
The motor data identification routine is carried out after the next switch-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parameters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
p1910 = 20:
Only for internal SIEMENS use.
Value:
0:
Inhibited
1:
Complete identification (ID) and acceptance of motor data
2:
Complete identification (ID) of motor data without acceptance
20:
Voltage vector input
21:
Voltage vector input without filter
22:
Rectangular voltage vector input without filter
23:
Triangular voltage vector input without filter
24:
Rectangular voltage vector input with filter
25:
Triangular voltage vector input with filter
26:
Enter voltage vector with DTC correction
27:
Enter voltage vector with AVC
28:
Enter voltage vector with DTC + AVC correction
Dependency:
"Quick commissioning" must be carried out (p0010 = 1, p3900 > 0) before executing the motor data identification
routine!
When selecting the motor data identification routine, the drive data set changeover is suppressed.
See also: p1900
See also: F07990, A07991
NOTICE
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data
identification routine is carried out as follows at the next switch-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
545