p2099[0...1]
CI: Connector-binector converter signal source / Con/bin S_src
Access level: 3
Calculated: -
Data type: Unsigned32 /
Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2468, 9360
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
See also: r2094, r2095
Note
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
p2100[0...19]
Change fault response fault number / Chng resp F_no
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
0
Max:
65535
Factory setting:
0
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
See also: p2101
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]
Change fault response response / Chng resp resp
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
0
Max:
6
Factory setting:
0
Description:
Sets the fault response for the selected fault.
Value:
0:
NONE
1:
OFF1
2:
OFF2
3:
OFF3
5:
STOP2
6:
Internal armature short-circuit / DC braking
Dependency:
The fault is selected and the required response is set under the same index.
See also: p2100
NOTICE
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
Parameters
7.3 Parameters
SINAMICS G120XA converter
576