p0040
Reset energy consumption display / Energy usage reset
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency:
See also: r0039
Note
When this display is reset (p0040), then the process energy display (r0042) is also reset.
r0041
Energy consumption saved / Energy cons saved
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [kWh]
Max:
- [kWh]
Factory setting:
- [kWh]
Description:
Displays the saved energy referred to 100 operating hours.
Dependency:
See also: p0040
Note
This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
r0042[0...2]
CO: Process energy display / Proc energy disp
Access level: 2
Calculated: -
Data type: Integer32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [Wh]
Max:
- [Wh]
Factory setting:
- [Wh]
Description:
Display and connector output for the energy values at the output terminals of the power unit.
Index:
[0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency:
See also: p0043
Note
The signal can be displayed as process variable (scaling: 1 = 1 Wh).
This is enabled in p0043.
The display is also reset with p0040 = 1.
If an enable is present in r0043 when the Control Unit powers up, then the value from r0039 is transferred into r0042.
As r0039 serves as a reference signal for r0042, due to format reasons, the process energy display can only process
values of r0039 up to 2147483 kWh. r0039 should also be reset using this value.
Parameters
7.3 Parameters
SINAMICS G120XA converter
360
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB