NOTICE
The time comprises r2130 (days) and r0948 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
r0949[0...63]
Fault value / Fault value
Access level: 3
Calculated: -
Data type: Integer32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8060
Min:
-
Max:
-
Factory setting:
-
Description:
Displays additional information about the fault that occurred (as integer number).
Dependency:
See also: r0945, r0947, r0948, r2109, r2130, r2133, r2136, r3120, r3122
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
p0952
Fault cases counter / Fault cases qty
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6700, 8060
Min:
0
Max:
65535
Factory setting:
0
Description:
Number of fault situations that have occurred since the last reset.
Dependency:
The fault buffer is deleted (cleared) by setting p0952 to 0.
See also: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
r0964[0...6]
Device identification / Device ident
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the device identification.
Index:
[0] = Company (Siemens = 42)
[1] = Device type
[2] = Firmware version
[3] = Firmware date (year)
[4] = Firmware date (day/month)
[5] = Number of drive objects
[6] = Firmware patch/hot fix
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
457
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......