r3120[0...63]
Component fault / Comp fault
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8060
Min:
0
Max:
3
Factory setting:
-
Description:
Displays the component of the fault which has occurred.
Value:
0:
No assignment
1:
Control Unit
2:
Power Module
3:
Motor
Dependency:
See also: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3122
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r3121[0...63]
Component alarm / Comp alarm
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8065
Min:
0
Max:
3
Factory setting:
-
Description:
Displays the component of the alarm which has occurred.
Value:
0:
No assignment
1:
Control Unit
2:
Power Module
3:
Motor
Dependency:
See also: r2110, r2122, r2123, r2124, r2125, r2134, r2145, r2146, r3123
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r3122[0...63]
Diagnostic attribute fault / Diag_attr fault
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8060
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the diagnostic attribute of the fault which has occurred.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Hardware replacement recommended
Yes
No
-
15
Message has gone
Yes
No
-
16
PROFIdrive fault class bit 0
High
Low
-
17
PROFIdrive fault class bit 1
High
Low
-
18
PROFIdrive fault class bit 2
High
Low
-
19
PROFIdrive fault class bit 3
High
Low
-
20
PROFIdrive fault class bit 4
High
Low
-
Dependency:
See also: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120
Parameters
7.3 Parameters
SINAMICS G120XA converter
640
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Summary of Contents for SINAMICS G120XA
Page 2: ......
Page 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Page 917: ......